LP-1 - auxiliary contact
Application:
Auxiliary contacts type LP-1 are designed to work with indoor disconnectors, switch disconnectors and earthing switches of medium voltage distribution network. The use of auxiliary contacts allows to obtain the information about the status of indoor device.
The contacts can be used to send a clear signal about the state of the position of apparatus for automation systems. They can also be used to any kind of blockades in switchgears.
Standard number of the auxiliary contacts is 16 (8NC + 8 NO).
Advantages:
- simple design
- standard contacts
- small size
- the ability to adjust the angle of operation
- the ability to determine different combinations of switching contacts
Technical data:
PARAMETER | VALUE |
rated insulation voltage | 500 V |
rated DC current | 6 A |
switching durability | 1000000 |
operating temperature | 5°C up to 50°C |
operating position | any |
level of protection | IP 20 |
Auxiliary contacts are available in various configurations:
- LP-1 8- 4NC+4NO
- LP-1 12- 6NC+6NO
- LP-1 16- 8NC+8NO
- LP-1 20- 10NC+10NO
Configuration of the auxiliary contact’s contacts LP-1:
C1 | 25 | 28 | 31 | 34 | 37 | 40 | 43 | 46 |
NO | 27 | 30 | 33 | 36 | 39 | 42 | 45 | 48 |
NC | 26 | 29 | 32 | 35 | 38 | 41 | 44 | 47 |
NC | 2 | 5 | 8 | 11 | 14 | 17 | 20 | 23 |
NO | 3 | 6 | 9 | 12 | 15 | 18 | 21 | 24 |
C1 | 1 | 4 | 7 | 10 | 13 | 16 | 19 | 22 |
Standard auxiliary contacts:
All technical data presented in the catalog can be changed due to technological progress.
Download:
Generate a catalog card (beta):