OWPS - indoor rotary disconnector
Application:
OWPS type disconnectors are devices used to connecting and disconnecting the electrical circuit without a load. Devices of this type are used in traction and in the industry. Mounted in a chamber, disconnector OWPS meets various roles such as:
- isolating the positive or negative end, or both assembly of transformer/ rectifier
- power supply isolation from the source of energy
Thanks to its modular design, disconnector OWPS allows for a large number of different combinations and option, which allows it to carry out many functions.
Advantages:
- thermal current in open air: 1600 A up to 6300 A
- rated voltage: 1800 VDC i 3600 VDC
- high level of rated insulation voltage: 3000 VDC and 4800 VDC
- high rated short-circuit strength
- connections silver plated
- self-cleaning contacts
- controlled manually or by motor
- auxiliary contacts: 3NO+3NC, 6NO+6NC
- compliance with standards: PN-EN 50123-2:2013, PN-EN 50123-3:2003
Operating conditions:
MINIMUM MECHANICAL DURABILITY |
20000 cycles |
AMBIENT TEMPERATURE |
- 5 up to + 40⁰C |
ALTITUDE ABOVE SEA LEVEL |
1500 m |
TIME OF MECHANICAL OPENING |
< 2 s. |
TIME OF MECHANICAL CLOSING |
< 2 s. |
LEVEL OF PROTECTION |
IP00 |
Auxiliary contacts:
Auxiliary contacts are based on the main panel of the disconnector. Contacts have 3 or 6 pairs of auxiliary contacts NO/NC.
NUMBER OF CONTACTS |
3, 6 pairs of NO/NC |
RATED OPERATING VOLTAGE |
24 - 230 VDC |
RATED CURRENT |
0,27 A |
MIN. LEAKAGE CURRENT AT 24 VDC |
10 mA |
Construction:
The OWPS type disconnector is made of an aluminum base, copper busbars, silver contacts, post insulators, electrically insulating strings and a drive (motor or manual). Disconnector equipped with electric drive can operate in vertical or horizontal position. Mounted in cells on busbars and terminal insulators for visible and safe insulation clearance.
Marking:
NAME OF DISCONNECTOR |
OWPS |
- |
. |
- |
. |
- |
. |
- |
- |
. |
- |
RATED VOLTAGE |
- |
18 |
. |
- |
. |
- |
. |
- |
- |
. |
- |
THERMAL CURRENT |
- |
- |
. |
20 |
. |
- |
. |
- |
- |
. |
- |
NUMBER OF POLES |
- |
- |
. |
- |
. |
1 |
. |
- |
- |
. |
- |
DRIVE |
- |
- |
. |
- |
. |
- |
. |
M |
- |
. |
- |
DRIVE’S VOLTAGE |
- |
- |
. |
- |
. |
- |
. |
- |
2 |
. |
- |
NO. OF AUXILIARY CONTACTS |
- |
- |
. |
- |
. |
- |
. |
- |
- |
. |
3 |
PROPER MARKING |
OWPS |
18 |
. |
20 |
. |
1 |
. |
M |
2 |
. |
3 |
DISCONNECTOR | OWPS | |
RATED VOLTAGE | 1800 VDC | 18 |
3600 VDC | 36 | |
THERMAL CURRENT IN OPEN AIR | 1600 A | 16 |
2000 A | 20 | |
2500 A | 25 | |
4000 A | 40 | |
6300 A | 63 | |
NUMBER OF POLES | 1 | 1 |
2 | 2 | |
DRIVE | manual | H |
motor | M | |
DRIVE'S VOLTAGE | manual drive | 0 |
24 V DC | 1 | |
220 V DC | 2 | |
230 V AC | 3 | |
NUMBER OF AUXILIARY CONTACTS | 3 NO + 3 NC | 3 |
6 NO + 6 NC | 6 |
Example of order:
Indoor disconnector OWPS 18.20.1.M.2:
- Indoor disconnector, rated voltage 1,8 kV DC; rated current 2000 A, monopolar, with motor drive with operating voltage 220 V DC and with auxiliary contacts 3 NO + 3 NC
Indoor disconnector OWPS 36.25.2.H.0.6:
- Indoor disconnector, rated voltage 3,6 kV DC; rated current 2500 A, 2-poles, with manual drive and with auxiliary contacts 6 NO + 6 NC
Due to technical reasons you can not combine some options and configuration in marking.
Technical drawings:
All technical data presented in the catalog can be changed due to technological progress.