OWPS GE-B - reinforced indoor rotary disconnector
Application:
OWPS GE-B is reinforced version of OWPS. It is more robust and able to reach short peak current (Ik=280kA/tk=40ms). This could be achieved thanks to use of legally protected construction of layer insulators. OWPS GE -B type disconnectors are devices used to connecting and disconnecting the electrical circuit without a load. Devices of this type are used in traction, power banks and in the grid industry. Mounted in a chamber, disconnector OWPS GE-B meets various roles such as:
- isolating the positive or negative end, or both assembly of transformer/ rectifier
- power supply isolation from the source of energy
Thanks to its modular design, disconnector OWPS GE-B allows for a large number of different combinations and option, which allows it to carry out many functions.
Advantages:
- thermal current in open air: 2000 A up to 6300 A
- rated voltage: 1800 VDC
- rated insulation voltage: 3000 VDC
- high rated short-circuit strength
- connections silver plated
- self-cleaning contacts
- controlled manually or by motor
- auxiliary contacts: 3NO+3NC, 6NO+6NC
- compliance with standards: PN EN 50123-2:2013, PN-EN 50123-3:2003
Characteristic:
- thermal current in open air: 2000 A up to 6300 A
- rated voltage: 1800 VDC
- high level of rated insulation voltage: 3000 VDC
- high rated short-circuit strength
- connections silver plated
- self-cleaning contacts
- controlled manually or by motor
- auxiliary contacts: 3NO+3NC, 6NO+6NC
- compliance with standards: PN-EN 50123-2:2013, PN-EN 50123-3:2003
Operating conditions:
MINIMUM MECHANICAL DURABILITY |
20000 cycles |
AMBIENT TEMPERATURE |
- 5 up to + 40⁰C |
ALTITUDE ABOVE SEA LEVEL |
1500 m |
TIME OF MECHANICAL OPENING |
< 2 s. |
TIME OF MECHANICAL CLOSING |
< 2 s. |
LEVEL OF PROTECTION |
IP00 |
Auxiliary contacts:
Auxiliary contacts are based on the main panel of the disconnector. Contacts have have 3 or 6 pairs of auxiliary contacts NO/NC.
NUMBER OF CONTACTS |
3, 6 pairs of NO/NC |
RATED OPERATING VOLTAGE |
24 - 230 VDC |
RATED CURRENT |
0,27 A |
MIN. LEAKAGE CURRENT AT 24 VDC |
10 mA |
Construction:
OWPS GE-B disconnectors consist of aluminum base, coppery busbars, silver contacts, post insulators, electroinsulating strings and the motor drive. They are equipped with electric drive. The disconnectors can work in vertical or horizontal position.
Marking:
NAME OF DISCONNECTOR |
OWPS GE-B |
- |
. |
- |
. |
- |
. |
- |
- |
. |
- |
RATED VOLTAGE |
- |
18 |
. |
- |
. |
- |
. |
- |
- |
. |
- |
THERMAL CURRENT |
- |
- |
. |
20 |
. |
- |
. |
- |
- |
. |
- |
NUMBER OF POLES |
- |
- |
. |
- |
. |
1 |
. |
- |
- |
. |
- |
DRIVE |
- |
- |
. |
- |
. |
- |
. |
M |
- |
. |
- |
DRIVE’S VOLTAGE |
- |
- |
. |
- |
. |
- |
. |
- |
2 |
. |
- |
NO. OF AUXILIARY CONTACTS |
- |
- |
. |
- |
. |
- |
. |
- |
- |
. |
3 |
PROPER MARKING |
OWPS GE-B |
18 |
. |
20 |
. |
1 |
. |
M |
2 |
. |
3 |
DISCONNECTOR | OWPS GE-B | |
RATED VOLTAGE | 1800 VDC | 18 |
THERMAL CURRENT IN OPEN AIR | 2000 A | 20 |
2500 A | 25 | |
4000 A | 40 | |
NUMBER OF POLES | 1 | 1 |
DRIVE | motor | M |
DRIVE'S VOLTAGE | 24 V DC | 1 |
220 V DC | 2 | |
230 V AC | 3 | |
NUMBER OF AUXILIARY CONTACTS | 3 NO + 3 NC | 3 |
6 NO + 6 NC | 6 |
Example of order:
Indoor disconnector OWPS GE-B 18.20.1.M.2:
- Indoor disconnector, rated voltage 1,8 kV DC; rated current 2000 A, monopolar, with motor drive with operating voltage 220 V DC and with auxiliary contacts 3 NO + 3 NC
Due to technical reasons you can not combine some options and configuration in marking.