RW 12 / 24 / 42 kV - 3-pole indoor load break switch
Application:
Indoor load break switches type RW and set of switch disconnectors with fuses type RW are used in indoor switchgears (voltage of 7,2-42 kV). They are designed to turn on and off currents do not exceed their rated current. The switch disconnectors with fuses type RWB have the ability to turn off short-circuit currents by cooperating with fuse disconnectors.
In the open state switches create the visible isolating clearance.
Construction and operation:
RW-type switches are three-pole devices with secant movement of blade of current path. The apparatus has modular design. The permanent contacts are made of copper flat, covered with a layer of silver. High technical parameters are the result of the applied solution of the main path coupled with arcing contact. Opening and closing the arcing contacts is delayed compared to the main contacts (movable). During the shutdown process, arc quenching occurs at the arcing contact. Quenching occurs due to the compressed air outlet, through a nozzle (automatically when opening) connected by rapid streching of the arc.
The speed of closing and opening of the disconnector is independent of the operating speed. This is ensured by a step mechanism when closing and a spring mechanism when opening. Reinforcement of the step and storage mechanism is carried out by means of a motor or manual drive, after which both mechanisms are simultaneously reinforced during the closing process. The load break switches RW can be driven by manual drives NR1-01, NRWO-4, NR-3 as well as by motor drives NS-EL 30-03, NSP 30-04.
Advantages:
- modular design
- the possibility of building the drives of plane and rotory motion of the string
- the possibility of choosing the side of mounting the drive (left-right)
- cooperation with motor drives NS-EL 30-03, NSP 30-04 and manual drives NR-1, NRWO-4, NR-3
- reliability
- high technical parameters
- possibility of equipping the switch with reactance insulators 12; 17,5; 24, 42 kV, electromagnetic release 24; 48; 110; 220 V AC/DC, auxiliary contacts showing the position of the device
Technical data:
PARAMETER |
RW/RWB-12 |
RW/RWB-24 |
RW/RWB 42 kV |
|
1 |
rated operating voltage |
12 kV |
24 kV |
42 kV |
2 |
rated frequency |
50 Hz |
50 Hz |
|
3 |
DC rated current |
630 A |
630 A |
|
4 |
operating switching capacity:
|
|
|
|
5 |
max. current of fuse switch disconnector |
200 A |
200 A |
200 A |
6 |
rated short-circuit current |
63 kA |
63 A |
63 A |
7 |
withstand peak current |
63 kA |
63 kA |
63 kA |
8 |
withstand peak current 3 s. |
25 kA |
25 kA |
25 kA |
9 |
resistance of the current path |
60 μΩ |
65 μΩ |
65 μΩ |
10 |
test voltage (50Hz) for insulation:
|
|
|
|
11 |
impulse test voltage for insulation:
|
|
|
|
12 |
weight:
|
|
|
|
13 |
mechanical durability |
2000 cycles |
2000 cycles |
2000 cycles |
TECHNICAL DRAWINGS: